â— After the product arrives, the user should first check the packaging quality of the product. The package should be intact and the mark should be clear. If the package has obvious damage, the storage and transportation department should promptly identify the problem and responsibility and notify the company. If the package has no quality problems, the product can be removed from the box. Simple instrumentation can be performed if necessary;
â—Anti-corrosion chemical level gauge remove the float chamber flange. Put the float in the upward direction of the arrow (the upper part of the magnetic steel in the float is at the upper part), and reinstall the float chamber flange. Pay attention to the gasket. And evenly tighten, the lower flange is blocked, the water has the upper connection flange mouth slowly injected into the float chamber, the indicator should have liquid level indication and sensitive and no jump, the instrument is normal, if the indicator is tracking indication, available The spare tool magnet attracts the indicating float to couple it with the magnetic float in the float chamber (float indicator) or draws the indicator from bottom to top with magnetic steel to make it correct.
â— When the anti-corrosion chemical level gauge is installed on the equipment, the gasket should be installed on the flange joint surface, and then the bolt should be used to fix the meter on the user flange. When the instrument is installed on the pressure vessel, the pressure test shall be carried out together with the container according to the relevant regulations, that is, the hydrostatic test after 1.25 times of working pressure and the airtightness test of 1.05 times of working pressure, and it is confirmed that there is no leakage before it can be put into use. (Note that when the experimental pressure exceeds 1.25 times the working pressure of the instrument, the float should be taken out of the float chamber. After the water pressure test is passed, the float is placed in the float chamber for a gas tightness test of no more than 1.05 times the working pressure of the instrument).
â— When the instrument is put into operation, open the upper valve and then slowly open the lower valve to allow the medium to slowly flow into the float chamber to prevent the liquid level from rising too fast and the indicator cannot track or damage the float.
â— For anti-corrosion chemical level gauges with liquid level transmitter (electric signal remote transmission), the spare tool magnet should be used to attract the magnetic chamber movement of the float chamber, simulate the liquid level change, and detect the liquid level transmitter work. Is it normal? For explosion-proof instruments, not only the operating state parameters of the transmitter but also the explosion-proof performance of the detector (such as the strength of the explosion-proof casing, coating, sealing, etc.) must be detected.
â— The installation of the top-mounted anti-corrosion chemical level gauge should first install the float rod assembly, move the float ball by hand, simulate the liquid level change, and the indicator should be able to operate normally. When installing the instrument, first insert the float rod assembly into the pontoon through the instrument flange hole, and make the magnetic steel N pole (sealing surface) on the float rod face the indicator. After adding the gasket, the long board and the instrument on the assembly After the long end of the flange end face is aligned, connect the two flanges.
â—High temperature and high pressure type anti-corrosion chemical level meter:
a. Install the whole table according to the assembly drawing: the insulation gasket on the small flange between the pads, and use the spare M12 bolts, nuts and gaskets. Install the copper pipe at the specified location, the joint is tightened and must not leak.
b. When installing the instrument on the equipment, install the gasket on the flange joint surface, and then bolt the instrument to the predetermined flange of the user equipment interface.
c. After the instrument is installed, open the valve to pressurize the instrument. Pay attention to the pressure to be slow! Wait for the pressure temperature of the container and the instrument chamber to stabilize, and the instrument can be put into use behind.
â— Anti-corrosion chemical level gauge with liquid level transmission output:
a. When installing instruments with explosion-proof requirements, the user must abide by the "Electrical Safety Regulations for Hazardous Locations in the People's Republic of China"; maintenance must be carried out in a safe place. The power must be switched off during installation and maintenance. After confirming that the power is off, open the instrument junction box. The ground terminal on the instrument's junction box must be connected to a reliable ground wire. During the adjustment and use, care should be taken to protect the explosion-proof threaded joint surface on the instrument junction box, and there must be no scratches or collisions.
b. After the on-site display part of the instrument is put into operation, connect the liquid level to the transmitter of the output level gauge and connect the instrument junction box to confirm that the seal can be energized.
c. Observe the liquid level value of the digital display. If the liquid level value of the liquid level transmission output level gauge is inconsistent with the liquid level value displayed on the spot, you can loosen the hose clamp and adjust the upper and lower positions of the liquid level transmitter. Until the agreement is reached. Then tighten the hose clamp.
d. The level gauge alarm switch with alarm switch is a dry contact passive switch. The switch can be roughly divided into normally open, normally closed, normally open and self-locking. Mainly used to control small power loads (relays, contactors, etc.). Note: The switch type and switch capacity are in accordance with the contract.
â— The measurement zero point of the anti-corrosion meter is based on the position indicated by the actual indicator. The anti-corrosion type instrument whose main material is PVC or the like has low mechanical strength, and should be externally supported by metal to ensure safe use. Care should also be taken during installation to evenly tighten the flange screws to protect them from damage caused by uneven forces.
â—The operating principle of the liquid level transmission part (electrical part) of the flameproof liquid level gauge explosion-proof liquid level gauge: it is the change of the number of resistors connected to the loop caused by the magnetic float on the reed switch. The resistance portion corresponding to the liquid level change can be caused to occur in the sensor portion. Through the signal converter, the resistance signal can be converted into a 4-20 mA current signal.
The electronic components of this level gauge have almost no energy storage components such as capacitors and inductors. And the performance is stable. The flameproof box has good sealing performance.
The transmitter output terminals of the level gauge are 1 and 2, where: 1 is the negative pole and 2 is the positive pole. The wires are connected from the 1 and 2 ends and the wires are connected to other secondary level gauges. Pay attention to the positive and negative poles when connecting!
â—Intrinsically safe level gauge The working principle of the liquid level transmission part (electrical part) of the intrinsic safety level gauge: it uses a magnetic float to act on the reed switch, and the on/off of the reed switch causes the resistance value of the loop. The change (the number of precision resistors connected to the system changes), and in turn, the sensor portion can generate a resistance signal corresponding to the change in the liquid level. Through the signal converter, the resistance signal can be converted into a 4-20 mA current signal.
The electronic components of this level gauge have almost no energy storage components such as capacitors and inductors. And the performance is stable. The transmitter output terminals of the level gauge are 1 and 2, where: 1 is the negative pole and 2 is the positive pole. The wires are connected from the 1-terminal and 2-terminal connections, and the wires are connected to a safety barrier located in the safety zone. Pay attention to the positive and negative poles when connecting!
In the process of using the site, there is any place that does not understand or need technical guidance. You can contact us at any time. Jiangsu Aoke Instrument Co., Ltd. specializes in instrumentation work for more than 10 years. You can contact us at any time during product selection and on-site installation. !